C-GIS SF6 MV switchgear

Release Time:2026-06-01 08:01:03 Views:248
  • C-GIS SF6  MV switchgear

General Description

UN3-36/40.5 gas-insulated MV switchear is designed and manufactured in accordance with GB and IEC standards. With fully insulated and hermetically sealed construction, it adapts to severe working conditions such as pollution, salt fog, high humidity and high altitude; multiple configuration schemes are available to satisfy extra stringent site requirements.

Typical Applications

  • Onshore & offshore wind farm step-up substations with 33kV/35kV grid connection;
  • Onshore & offshore energy storage and photovoltaic step-up substations with 33kV/35kV grid connection;
  • Step-up and step-down transformation & distribution substations for 33kV/35kV power networks.

Product Features

  • Designed and produced complying with relevant GB and IEC standards;
  • Equipped with vacuum interruption and fully SF₆ gas-insulated structure;
  • Gas tank with IP67 protection grade; no SF₆ refilling required during installation and whole service life under normal operation;
  • Suitable for installation at altitude up to 5000 m above sea level;
  • Capable of operating in industrial polluted, salt-foggy and humid environment: corrosion class C3 for onshore application and C4 for offshore application.

Service Ambient Conditions

  • Altitude: ≤5000 m. Special technical specification shall be specified if operating altitude exceeds 2000 m;
  • Ambient temperature: Max. +50℃, Min. -50℃; 24-hour average temperature ≤35℃;
  • Ambient humidity: 24h average relative humidity ≤95%; monthly average relative humidity ≤90%;
  • Electromagnetic interference: Induced interference amplitude on secondary circuit ≤1.6 kV;
  • Installation environment: No explosive or corrosive gas in ambient air; no frequent severe vibration or impact at installation site.
Note: Customized design can be negotiated with our company for working conditions beyond above scope.

Applicable Standards

  • IEC 62271-1:2017 & GB/T 11022-2020: Common specifications for high-voltage switchgear and controlgear
  • IEC 62271-200:2011 & GB/T 3906-2020: AC metal-enclosed switchgear and controlgear for 3.6kV ~ 40.5kV
  • IEC 62271-100:2017 & GB/T 1984-2014: High-voltage alternating current circuit-breakers
  • IEC 62271-105:2021 & GB/T 16926-2009: High-voltage AC switch-fuse combinations
  • IEC 62271-102:2001+A1:2011 & GB/T 1985-2014: High-voltage AC disconnectors and earthing switches (corrected typo IEC16271→IEC62271 per industry standard)
  • IEC 60529 & GB/T 4208-2017: Degrees of protection provided by enclosures (IP Code)
  • GB/T 11023-2018: Test method for SF₆ gas tightness of high-voltage switchgear
  • DL/T 402-2016: Technical order specification for high-voltage AC circuit breakers
  • DL/T 486-2021: Technical order specification for high-voltage AC disconnectors and earthing switches
  • DL/T 403-2017: Purchase specification for 12kV~40.5kV high-voltage vacuum circuit breakers
  • DL/T 404-2018: AC metal-enclosed switchgear and controlgear for 3.6kV~40.5kV
  • DL/T 593-2016: Common technical specifications for high-voltage switchgear and controlgear

Function Description

  1. Side outgoing main busbar: rated current options of 1250A and 2500A
  2. Independent busbar compartment: configurable with single or double gas tank layout
  3. Three-position disconnector with operating mechanism: manual or motorized operation available
  4. Circuit breaker and its operating mechanism: spring operated breaker with auto-reclosing function; manual or motorized charging for spring
  5. Mounting of cable terminals and surge arrester: adopted with C-type cable terminal; optional configuration: one set of cable plus arrester or two sets of cables plus arresters
  6. Cable compartment: compatible with installation of various specification power cables
  7. Pressure relief channel for cable compartment
  8. Pressure relief channel for gas tank
  9. Circuit breaker compartment
  10. Inter-compartment bushing
  11. Nameplate
  12. Mimic busbar diagram
  13. Protection relay unitUnifortuneTechnical Specification: